Full text
412. Each sample taken sent to an accredited laboratory must be accompanied by a sending form duly completed. The form must include the following information:
(1)  the address where the water cooling tower facility is located;
(2)  the name and contact information of the owner of the water cooling tower facility;
(3)  the identification number of the water cooling tower facility assigned by the Board;
(4)  the date and time of sampling and the water temperature;
(5)  the name and signature of the sampler;
(6)  the reference and location of the point of sampling;
(7)  the nature and concentration of treatment products; and
(8)  the date and time of the last injection of treatment products in the network of the water cooling tower facility, if such injection is not continuous.
O.C. 454-2014, s. 4.